Effect on tip load of large pole plants such as pole mounted transformers are calculated as:




Ftip = P * A* (hplant / hpole)


Where

Ftip = Pole tip load (kN)

P = Design wind pressure on plant  (kPa)

A = Area of plant exposed to wind (m2)

hplant = Center height of plant equipment (m)

hpole = Pole height above ground (m) 


Note:

Power Lines Pro currently does not account for the vertical force - only the wind pressure.


See Also:

Tip Load Calculation